Room-Level PAC 30-50kw DTCRA Series

DTCRA / DTCRC Series Precision Air Conditioner Air-cooled and chilled-water precision air conditioner for large data centers.

The DTCRA series includes air-cooled DTCRA and chilled-water DTCRC models. Air-cooled units cover 25–100 kW, while chilled-water units cover 30–200 kW. Modular combination enables flexible capacity matching, with down-supply and top-supply air modes available. It is applied in large data centers, central data centers, substations, and heavy-load equipment rooms. It supports customization for heating, humidification, and multiple supply/return air modes, and features large air volume, small enthalpy difference, high sensible heat ratio, EC fans, electronic expansion valves, R410a, and full alarm protection (power, water leakage, T&H over-limit, component protection). A 7-inch color touch screen, RS485/Modbus, group control up to 32 units, and remote monitoring are provided as standard.

Room-Level PAC 30-50kw DTCRA Series
Home > Products > Precision Air Conditioner > Room-Level PAC > Room-Level PAC 30-50kw DTCRA Series

Product Feature

Modular Flexible Capacity MatchingModular Flexible Capacity Matching

  • The modular unit design allows multiple modules to be freely combined for customized cooling output. Down-supply and top-supply air modes adapt to different data center air duct layouts. Air-cooled and chilled-water versions are available for different site resource conditions.

High-Performance Core ComponentsHigh-Performance Core Components

  • High-reliability scroll compressors provide low-noise and low-vibration operation.
  • Optional aviation-composite corrosion-resistant EC fans improve efficiency.
  • Electronic expansion valves deliver precise refrigerant flow control. PTC heating and large-capacity electrode humidification ensure stable temperature and humidity adjustment.

Powerful Group-Control IntelligencePowerful Group-Control Intelligence

  • A 7-inch high-precision color touch HMI supports group control of up to 32 units for centralized scheduling. A complete alarm diagnosis system is provided. Local display and remote monitoring linkage facilitate unified O&M management in large data centers.

Structure and Composition

Data Sheet

ROOM-LEVEL AIR COOLING PARAMETERS (CRA*URH/DRH/BRH)
MODEL DT
CRA***URH/DRH/BRH
025030035040045050042052062072082092102
Total Cooling Capacity Kw253036404550405162728192102
Visible Cooling Capacity Kw22.42832.435.941.346.435.946.855.365.373.483.894.3
Fan TypeEC Fan
Number Of Fans1111112222222
Blowing Rate m³/h780092001050011500128001350011800156001840021000230002560027000
Exhaust Pressure patreetop (025-050) / Nozzle residual pressure (042) / 20pa,20-300pa ok (052-082) / transfer (092-102)
Air FilterG4
Compressor TypeVortex Compressor
Number Of Compressor1111112222222
Type Of RefrigerantR410A
Electric Of Compressors TypePTC ELECTRICAL HEATING
Electrical Heating Kw666999999991515
Electric Heating Current A10101014141414141414142323
Type Of HumidifierElectricity (025-050) / Add saturated steam (042) / WET (052-102)
Electrode Humidification Kg/H5558888131313131313
Electrode Humidification Current A66610101010151515151515
Power Supply Type380V/50Hz 3N~
Full Load Current A37.94147.253.96061.658.366.677.589.8100.4115.4118.6
Condensate Drainage Dn MmG1/2"
Refrigerant Gas Pipe Mm18
Coolant Liquid Pipe Mm18
Tablet Outdoor Unit (CY*AISP)0451052205820662074208320281045105220582066207420832
Tablet Outdoor Unit Quantity1111112222222
Compact Outdoor Unit (CY*AISP)—044105510661077108810882088211021102132215421762
Compact Outdoor Unit Quantity—111111111111


OUTDOOR UNIT PARAMETERS
DT
CY** AISP
0291035104510522058206620742083208930963
Input Voltage220V/1Ph/50Hz
Dimensions (mm)1115*1065*5451225*1165*5451315*1165*5452025*1015*5202325*1065*5202125*1065*5452325*1165*5452425*1165*5452625*1165*5453240*1165*545
Weight Kg100112115158172182206213252290
DT
CY** AISP
0441055106610771088108821102132215421762
Input Voltage380V/3Ph/50Hz
Dimensions (mm)1100*1100*19071225*1165*5451315*1165*5452025*1015*5202325*1065*5202125*1065*5452325*1165*5452425*1165*5452625*1165*5453240*1165*545

HIGH-QUALITY FRAMEWORK AND COMPONENTS
DT-CRC030040050060070080090100110
Total Cooling Capacity Kw28.539.547.855.865.278.585.395.3104.5
Visible Cooling Capacity Kw28.539.547.855.865.278.585.395.3104.5
Water Flow M³/H4.916.88.239.6111.2313.5214.6916.4218
Differential Pressure Kpa565364687454.861.267.670.9
Quantity111112222
Blowing Rate M³/H8900970011600125001330018000212002300024000
Air FilterG4
Electrode Humidification Kg/H5555513131313
Electrode Humidification Current A6666615151515
Electric Heating Current A101010101014141414
Electric Heating Kw (Optional)666669999
Power Supply Type380Vac/3Ph/50Hz
Full Load Current A5555510101010
Dimensions (mm)915*983*1975915*983*1975915*983*1975915*983*1975915*983*19751790*983*19751790*983*19751790*983*19751790*983*1975
Weight Kg254283285286305476477478526
Take Over Size DN324040405050505050
DT-CRC120130140150160170180190200
Total Cooling Capacity Kw113.8119.2125.6141.1150159167.1174.5185.3
Visible Cooling Capacity Kw113.8119.2125.6141.1150.2159167.1174.5185.3
Water Flow M³/H19.620.5321.6424.3125.8727.3928.7930.0631.92
Differential Pressure kPa78.686.688.575.881.782.989.593.496.5
Quantity222333333
Blowing Rate m³/h246002520026500326003520036800374003860039900
Air FilterG4
Electrode Humidification Kg/H131313131313131313
Electrode Humidification Current A151515151515151515
Electric Heating Kw (Optional)999121212121212
Electric Heating Current A141414191919191919
Power Supply Type380Vac/3Ph/50Hz
Full Load Current A101010151515151515
Dimensions (mm)1790*983*19751790*983*19751790*983*19752665*983*19752665*983*19752665*983*19752665*983*19752665*983*19752665*983*1975
Weight Kg528530570702705738750752753
Take Over Size DN505050505050505050